TM9T - Flashing Code 6

York Gas Furnace: TM9T

Re: Flashing Code 6

Code 6 = Pressure switch opened (Code 3) 4 times during a run cycle.

► This is a "Soft Lockout" which will automatically reset after 1 hour.

► There are 3 pressure switches on this furnace. 1LP (1st Stage Switch) and 3LP (Condensate Switch) are wired in series to the pressure switch input.

►The 2LP (2nd Stage Switch) wires in separately and will cause a Code 13 (NOT A CODE 3).


Qty Possible Causes:
Bad Inducer Motor
Water in Vent
6 Water in Inducer/Clogged Drain
Improper Condensate Drainage
Bad Pressure Switch
Water in Pressure Switch / Tubing


CHECKOUT:

1. Check Inducer Motor Operation


2. Check Pressure Switches


3. Check Condensate Drainage