TG8S - Flashing Code 4

York Gas Furnace: TG8S

Re: Flashing Code 4

If the limit control opens, the burners will be de-energized and the air circulation and vent blower will be turned on until the limit closes. The diagnostic light code for this is four short flashes followed by a pause.


Qty Possible Causes (From Most to Least Likely):
Dirty Air Filter
Clogged Evaporator Coil
Under-sized Ductwork
High Gas Pressure
Bad Limit
Blower Speed too Low


CHECKOUT:

1. Check Temperature Rise


2. Check Air Filter


3. Check Gas Pressure


4. Check Blower Speed


5. Check Duct Static Pressure

 

 



Article ID: 389
Last updated: 30 Oct, 2017
Revision: 4
Equipment -> Gas Furnaces -> York -> TG8S -> TG8S - Flashing Code 4
https://ghac.makekb.com/entry/389/