Carrier 90% Gas Furnace: 350MAV
Re: Flashing Code 31 / Fault Code 31
Diagnostic Light Sequence: 3-Short Flashes, 1-Long Flash (- - - , —)
► On Carrier 90% Furnaces, the Pressure switch may be wired in series with a Low Gas Pressure Switch.
Therefore, a Fault Code 31 is caused by one of the following:
- Pressure Switch failed to close or re-opened after closing.
- Low Gas Pressure Switch Open
Qty |
Possible Causes: |
|
Blocked Vent |
1 |
Bad Pressure Switch |
1 |
Bad Inducer Motor |
1 |
Clogged Pressure Port |
|
Clogged / Frozen Drain |
|
Item Stuck in Inducer Motor |
|
Bad Ignition Control |
|
Low Gas Pressure |
CHECKOUT:
1. Check Furnace Operation
- Start the furnace with a call for heat.
- It is common for a Carrier furnace to run the blower for 90 seconds and flash a Code 12 on start-up.
- Inducer motor should start and run.
2. Check Inducer Motor
- With a call for heat, check for 115VAC between the Black and White wires of the 3-pin plug for the inducer motor.
- No Power = Bad Control Board
- Power + No Inducer = Bad Inducer / Capacitor or Blocked Inducer Wheel
3. Check Safety Circuit
- Check for 24VAC between "24V Com" and the Orange wire on Pin #4 of the 9-pin plug.
- No Power = Bad Control Board
- Check for 24VAC between "24V Com" and the Yellow wire on Pin #2 of the 9-pin plug.
- Power on Pin #4 + Power on Pin #2 + Code 31 = Bad Control Board
- Power on Pin #4 + No Power on Pin #2 = Open Circuit ⇒ Check Safeties
- Pressure Switch
- Check for 24VAC between "24V Com" and both sides of the Pressure Switch.
- Power on Both Sides = Switch Closed ⇒ Check the Low Gas Pressure Switch
- Power on One Side Only = Open Switch ⇒ Check Pressures (below)
- Use a pressure gauge to check the differential pressure with the inducer operating. (Trip Point = 1.80" w.c.)
- Differential pressure near or below the trip point ⇒ Check the inducer and combustion box negative pressures individually.
- ► Look into the pressure ports to make sure they are not clogged.
- Low Inducer Pressure = Vent or Vent Motor Problem
- High Combustion Box Pressure = Intake Problem
- Low Gas Pressure Switch
- Check for 24VAC between "24V Com" and both sides of the Low Gas Pressure Switch (if used).
- Power on Both Sides = Switch OK
- Power on One Side but Not the Other = Open Switch ⇒ Check Gas Pressure