DNH - Cooling - Indoor Coil Frozen

York Package Unit: DNH

Re: Cooling - Indoor Coil Frozen

The unit is operating in the cooling mode. The compressor and condenser fan motor are operating and the suction line to the compressor and indoor coil are frozen.

Qty Possible Causes:
Bad Blower Motor
Bad Blower Capacitor
Bad Blower Wheel
Low Refrigerant Charge
1 Stuck Contactor
Bad Fan Relay
Dirty Coil/Filter

CHECKOUT:

1. Check System Operation


2. Check Blower Wheel, Motor & Capacitor

► The 2 - 4 Ton Models use a standard, PSC Motor. The 5 Ton Model uses a Variable-Speed, ECM Motor


3. Thaw the Coil


4. Check Filter & Indoor Coil


5. Check Refrigerant



Article ID: 359
Last updated: 30 Jan, 2023
Revision: 11
Equipment -> Package Units -> York -> DNH -> DNH - Cooling - Indoor Coil Frozen