Trane Package Unit: YCC
Re: Heating - Code 2 - Won't Ignite
The Trane YCC package unit uses an Ignition Control Board (IGN) with an on-board spark generator for all heating functions.
Code 2 = Ignition Failure (3 Attempts)
The control can be reset by:
- Cycling power to the unit.
- Cycling the call for "W"
- Automatic reset after 2 hours
Qty |
Possible Causes (From Most to Least Likely): |
|
Dirty flame sensor |
|
No Gas |
2 |
Clogged Burners/Orifice |
|
Bad Gas Valve |
|
Bad Ignition Control |
CHECKOUT:
1. Check Ignition
- Visually inspect the burners during ignition.
- Burners should light with little or no delay from the sparker to the flame sensor.
- Make sure the flame sensor comes in good contact with the flame.
- The glow plug should de-energize once flame is established.
- Glow plug does not de-energize = Bad Control Board
2. Check Gas Valve
- Check Inlet Pressure
- Turn off power to the furnace and close the gas safety shut-off valve.
- Hook-up a gas pressure gauge to the inlet test port of the gas valve.
- Open the gas safety shut-off and check gas pressure.
- Should be minimum of 5" w.c. for Nat. gas and 11" w.c. for propane.
- No pressure = Gas Shut-Off --> Check the Meter
- Low Pressure = Bad Meter or Regulator
- Re-apply power to the furnace and activate a call for heat.
- Check for 24VAC between the two gas valve feed wires at the time of ignition.
- No power = Bad Ignition Control or Bad Wires
- Make sure the inlet gas pressure stays above minimum when the gas valve energizes.
- Pressure drops below minimum = Bad Meter or Regulator
- Check Manifold Pressure
- Turn off power to the furnace and close the gas safety shut-off.
- Move the gas pressure gauge to the manifold (leaving) test port on the gas valve.
- Be sure to put the plug back in the inlet test port before proceeding!
- Open the gas safety shut-off valve and re-apply furnace power.
- Activate a call for heat and monitor the manifold gas pressure during an ignition attempt. (3-3.5" w.c. for Nat. Gas, 9-11" w.c. for LP)
- No Pressure = Bad Gas Valve
- Good Pressure + No Ignition = Clogged Burners/Orfice ⇒ Remove burners and clean spreaders. Also make sure that the burner orifices are not clogged.
3. Check Flame Sensor
- On the multi-meter:
- Switch the test leads to "COM" and "mA".
- Set the meter on DC 200ù.
- Disconnect the wire from the flame sensor.
- Place one meter lead on the flame sensor terminal and the other on the flame sensor wire.
- Check the reading when the burners ignite.
- Minimum acceptable reading = 1 MicroAmp
- Low Reading = Dirty Flame Sensor ⇒ Clean Flame Sensor & Re-check
- Normal Reading (2 to 6 mA) + Still Shuts-Off = Bad Ignition Control
- MOVE SENSOR LEADS BACK TO "COM" and "V" BEFORE PROCEEDING!