Goodman Package Unit: GPG13
Re: Low on Refrigerant / Freon
A package unit that is low on refrigerant indicates a refrigerant leak.
Qty |
Possible Causes (From Most to Least Likely): |
1 |
Leaking Indoor Coil |
|
Leaking Outdoor Coil |
|
Leaking Schrader |
|
Other Leak |
Step 1. Identify the Leak
- Leak-check the unit with an electronic leak detector to find the location of the leak.
Step 2. Leak Repair
- If the system has lost more than 2lbs over 1 year, the leaking component should be replaced.
- If the system has lost 2lbs or less over 1 year, Leak-Stop Dye should be added to the system.
- Manufacturer warranties do not pay for the addition of Leak-Stop