Rheem RPNL / RPQL - Low Pressure - Code L21 - Cooling

Rheem Heat Pump: RPNL / RPQL

Re: Cooling - Low Pressure Lockout - Code L21

These heat pump models have a control board which monitors equipment operation.

If the low pressure switch trips three times during a run-cycle, a "Hard-Lockout" Code L21 is generated and must be manually reset.


Qty Possible Causes:
1 Low Refrigerant Charge
Bad I/D Expansion Valve
Low/No Airflow
Cold Outdoor Air
Cold Return Air

CHECKOUT:

1. Check Refrigerant Pressures


2. Check Superheat and Sub-Cooling


3. Check Indoor Temperature Drop