York Heat Pump: Cooling
Re: Hi Pressure Fault + Hi Discharge Temperature Fault
When checking the fault history, the Yorkguard VI shows both a High Pressure and High Discharge Temperature fault.
A High Pressure Lockout is indicated by the following LED pattern on the outdoor unit control board:
- Green = Off
- Red = 1 Flash (Not in Lockout) or 2 Flashes (Lockout)
A High Temperature Lockout is indicated by the following LED pattern on the outdoor unit control board:
- Green = 5 Flashes
- Red = On
X/L Output
- 2 Flashes at Thermostat = Soft Lockout
- Switch opened two times in 6 hours.
- Reset by cycling thermostat or jumping Test pins.
- 3 Flashes at Thermostat = Hard Lockout
- Four Soft Lockouts in 12 hours.
- Reset by cycling 24VAC power to the board.
Qty |
Possible Causes: |
1 |
Stuck Contactor |
|
Refrigerant Over-Charge |
|
Bad I/D Expansion Valve |
CHECKOUT:
1. Check Outdoor Unit
- Make sure the thermostat is set correctly and calling for Cool.
- Remove the access panel of the outdoor unit.
- Check the Yorkguard VI for any active diagnostics.
- Reset if necessary by removing 24V R and Y from the board, the reconnecting.
- Speed-up the Anti Short-Cycle Delay timer by jumping the Test pins.
2. Check Contactor
- Cycle power to the contactor by removing the wire from the "M" or "M1" terminal on the Yorkguard VI board.
- If the contactor fails to disengage = Stuck Contactor
- Disconnect high voltage power to the outdoor unit by pulling the service disconnect.
- Look at the contact points of the contactor to see if the contactor is burnt and might be sticking.
3. Check Refrigerant Pressures
- Hook-up refrigerant gauges to the pressure ports on the unit.
- Allow the unit to run at least 10 minutes.
- Monitor pressures and temperature as the system operates.
Normal Pressure Range |
Refrigerant |
55-75 Deg O/D |
75-95 Deg O/D |
R410A |
- 110 - 130 Suction
- 225 - 300 Discharge
|
- 125 - 150 Suction
- 250 - 375 Discharge
|
4. Check Superheat and Sub-Cooling
- Superheat
- Check the Suction Line Temperature near the outdoor unit.
- Record the "Evaporation Temperature" from the Suction pressure gauge.
- Superheat = Suction Line Temperature - Evaporation Temperature
- Normal Superheat = 8 - 18 deg.
- Sub-Cooling
- Check the Liquid Line Temperature near the outdoor unit.
- Record "Saturation Temperature" from the discharge pressure gauge.
- Sub-Cooling = Saturation Temp - Liquid Line Temp
- Normal Sub-Cooling = 3 - 12 deg. (Sight-Glass Clear)
- Normal Suction Pressure + Normal Superheat + High Head Pressure + High Sub-Cooling (Clear Sight-Glass) = Refrigerant Over-Charge
- Low Suction Pressure + High Superheat + High Sub-Cooling (Clear Sight-Glass) = Bad I/D Expansion Valve
- Examine I/D Expansion Valve: An under-feeding valve should be frosting at the valve.
5. Check Discharge Temperature
- Connect a temperature thermistor to the compressor discharge line near the discharge sensor.
- Allow the system to run for about 10 minutes and watch the actual discharge temperature.
- Normal Discharge Temperature = 130 - 180 deg F.
- Trip Point = 250 deg. F.