Hi Pressure + Hi Discharge Temp Fault (Cooling)

York Heat Pump: Cooling

Re: Hi Pressure Fault + Hi Discharge Temperature Fault

When checking the fault history, the Yorkguard VI shows both a High Pressure and High Discharge Temperature fault.

A High Pressure Lockout is indicated by the following LED pattern on the outdoor unit control board:

A High Temperature Lockout is indicated by the following LED pattern on the outdoor unit control board:


X/L Output


Qty Possible Causes:
1 Stuck Contactor
Refrigerant Over-Charge
Bad I/D Expansion Valve


CHECKOUT:

1. Check Outdoor Unit


2. Check Contactor


3. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 55-75 Deg O/D 75-95 Deg O/D
R410A
  • 110 - 130 Suction
  • 225 - 300 Discharge
  • 125 - 150 Suction
  • 250 - 375 Discharge


4. Check Superheat and Sub-Cooling


5. Check Discharge Temperature