Heat Pump - Blown Fuse / Low Voltage Short - Cooling

Heat Pump: Cooling

Re: Blown Fuse / Low Voltage Short

Indications: A Blown Low Voltage Fuse or a Bad Transformer on the Air Handler


Qty Possible Causes:
  Shorted Control Wire To Stat
1 Shorted Control Wire To H/P
Bad Contactor
Shorted Pressure Switch Wiring
Bad Defrost Board
Bad Air Handler Board
Bad ECM Blower Motor
Shorted Sensor
Bad Thermostat

CHECKOUT:

1. Install Mini-Breaker


2. Isolate the Thermostat


3. Test Heat Pump Wiring

At the Air Handler, use a jumper wire to test each output as follows:


4. Test Thermostat


5. Test Thermostat Wiring



Article ID: 296
Last updated: 16 Nov, 2017
Revision: 5
Equipment -> Heat Pumps -> York -> YHJD/YHJF -> Cooling -> Heat Pump - Blown Fuse / Low Voltage Short - Cooling