Climatemaster - Code 2 / High Pressure Fault - Heating

Climatemaster Geothermal: Heating 

Re: Code 2 / High Pressure Fault

Code 2 = High Pressure Fault

When the high pressure switch opens due to high refrigerant pressures the compressor relay is de-energized immediately since the high pressure switch is in series with the compressor contactor coil.


Qty Possible Causes:
1 Refrigerant OverCharge
Bad Expansion Valve
Bad Blower Motor / Capacitor
Bad CFM Board
1 Low Indoor Airflow
Refrigerant Restriction
Bad Pressure Switch


CHECKOUT:

1. Check Indoor Airflow


2. Check Blower Motor


3. Check Operating Conditions

► Be sure to re-connect the 3-wire heater plug and HWG pump before closing the unit.


4. Check Air Filter & Indoor Coil


5. Check Duct Static Pressure



Article ID: 247
Last updated: 8 Feb, 2023
Revision: 20
Equipment -> GeoThermal -> Climatemaster -> TS/TT -> Diagnostics -> Climatemaster - Code 2 / High Pressure Fault - Heating