Climatemaster Geothermal: TS070 / TT072 / TE072
Re: Performance Chart
The following chart shows the design operating conditions of the heat pump WITH THE HWG OFF.
► The chart is based on 3 GPM/Ton and 70° Return Air Temperature.
COOLING | ||||||
EWT | Suction | Discharge | Superheat | Subcool | Water Rise | Air Drop |
60° | 128-138 | 245-265 | 13-18 | 14-19 | 10-12 | 24-30 |
70° | 128-138 | 290-310 | 13-18 | 14-19 | 10-12 | 23-29 |
80° | 132-142 | 320-340 | 10-15 | 14-19 | 9.2-11.2 | 22-28 |
90° | 135-145 | 350-370 | 10-15 | 13-18 | 8.5-10.5 | 22-28 |
100° | 139-149 | 401-421 | 9-14 | 13-18 | 8-10 | 21-27 |
110° | 144-154 | 452-472 | 9-14 | 13-18 | 7.4-9 | 20-27 |
HEATING | ||||||
EWT | Suction | Discharge | Superheat | Subcool | Water Drop | Air Rise |
30° | 68-78 | 300-320 | 10-15 | 15-20 | 3.5-5.5 | 21-27 |
40° | 87-97 | 325-345 | 10-15 | 12-17 | 4.5-6.5 | 26-32 |
50° | 106-116 | 348-368 | 10-15 | 9-14 | 5.7-7.7 | 30-36 |
60° | 125-135 | 370-390 | 10-15 | 10-15 | 6.8-8.8 | 34-40 |
70° | 144-154 | 395-415 | 10-15 | 11-16 | 7.9-9.9 | 38-44 |