Climatemaster Geothermal: TS048 / TT049 / TE049
Re: Performance Chart
The following chart shows the design operating conditions of the heat pump WITH THE HWG OFF and operating at FULL CAPACITY.
► The chart is based on 3 GPM/Ton and 70° Return Air Temperature.
| COOLING | ||||||
| EWT | Suction | Discharge | Superheat | Subcool | Water Rise | Air Drop |
| 60° | 128-138 | 238-268 | 9-14 | 5-10 | 10.1-12.1 | 19-25 |
| 70° | 131-141 | 270-290 | 9-14 | 5-10 | 9.9-11.9 | 19-25 |
| 80° | 134-144 | 311-331 | 9-14 | 4-9 | 9.6-11.6 | 18-24 |
| 90° | 136-146 | 352-372 | 7-12 | 4-9 | 9.3-11.3 | 18-24 |
| 100° | 139-149 | 399-419 | 7-12 | 3-8 | 8.9-10.9 | 17-23 |
| 110° | 142-152 | 447-467 | 7-12 | 3-8 | 8.5-10.5 | 17-23 |
| HEATING | ||||||
| EWT | Suction | Discharge | Superheat | Subcool | Water Drop | Air Rise |
| 30° | 72-82 | 292-312 | 7-12 | 9-14 | 4-6 | 19-25 |
| 40° | 87-97 | 309-329 | 7-12 | 9-14 | 5-7 | 22-28 |
| 50° | 103-113 | 326-346 | 8-13 | 10-15 | 5.9-7.9 | 25-31 |
| 60° | 115-125 | 343-363 | 8-13 | 9-14 | 7-9 | 28-34 |
| 70° | 137-147 | 361-381 | 9-14 | 9-14 | 7.9-9.9 | 30-37 |