Climatemaster Geothermal: TS024 / TT026 / TE026
Re: Performance Chart
The following chart shows the design operating conditions of the heat pump WITH THE HWG OFF and operating at FULL CAPACITY.
► The chart is based on 3 GPM/Ton and 70° Return Air Temperature.
COOLING
| EWT | Suction | Discharge | Superheat | Subcool | Water Rise | Air Drop |
| 60° | 135-145 | 210-250 | 7-12 | 4-9 | 7.5-9.5 | 19-25 |
| 70° | 136-146 | 253-273 | 7-12 | 4-9 | 7.6-9.6 | 19-25 |
| 80° | 137-147 | 298-318 | 7-12 | 4-9 | 7.4-9.3 | 18-24 |
| 90° | 139-149 | 340-360 | 6-11 | 5-10 | 7.2-9.2 | 18-24 |
| 100° | 141-151 | 385-405 | 6-11 | 5-10 | 6.8-8.8 | 17-23 |
| 110° | 143-153 | 433-453 | 6-11 | 5-10 | 6.5-8.5 | 17-23 |
HEATING
| EWT | Suction | Discharge | Superheat | Subcool | Water Drop | Air Rise |
| 30° | 78-88 | 277-297 | 6-11 | 3-8 | 2.7-4.7 | 18-24 |
| 40° | 89-99 | 286-306 | 7-12 | 4-10 | 3.6-5.6 | 20-26 |
| 50° | 110-120 | 305-325 | 8-13 | 6-11 | 4.5-6.5 | 23-29 |
| 60° | 130-140 | 314-334 | 9-14 | 7-12 | 5.2-7.2 | 25-31 |
| 70° | 141-151 | 334-354 | 10-15 | 8-13 | 5.8-7.8 | 28-35 |