Re: Unit Control Board - Diagnostic Codes
There are two control boards on this unit. The main unit controller mounted in the electrical control panel and the ignition control board mounted in the burner section.
Unit Control Fault Indicators | |
On | Control Failure - Replace Control |
Pulse | Normal Operation |
1 Flash | Not Applicable |
2 Flash | Control waiting (short-cycle delay) |
3 Flash | Compressor 1 HPS Lockout |
4 Flash | Compressor 2 HPS Lockout |
5 Flash | Compressor 1 LPS Lockout |
6 Flash | Compressor 2 LPS Lockout |
7 Flash | Compressor 1 FreezeStat Lockout |
8 Flash | Compressor 2 FreezeStat Lockout |
9 Flashes* | Ignition Control Fault |
10 Flashes | Compressor 1 off due to Low OA Temp |
11 Flashes | Compressor 2 off due to Economizer |
12 Flashes | Fan Overload Tripped |
13 Flashes | Low Voltage Detected |
14 Flashes | Control Failure |
Off | No Power or Control Failure |
* Code 9 - You must check the Ignition Control Board for the actual fault condition.