Predator RTU - Heat Control Board - Fault Codes

York Rooftop Units: DH, DM

Re: Heat Control Board - Diagnostic Codes

There are two control boards on this unit. The main unit controller mounted in the electrical control panel and the ignition control board mounted in the burner section.

► The main unit controller has one diagnostic (Code 9) to indicate a fault from the ignition control board. You must check the ignition control board for the actual fault condition.


Ignition Control Fault Indicators
Pulse
  • Normal Operation
2 Flash
  • Pressure switch open with inducer on
3 Flash
  • Pressure switch closed with inducer off
  • Rollout switch open
4 Flash
  • Limit switch open
  • Aux limit switch open
5 Flash
  • Flame present with gas off
6 Flash
  • Ignition lockout



Article ID: 240
Last updated: 14 Dec, 2018
Revision: 5
Equipment -> Rooftop Units -> York -> Predator DH, DM, -> Predator RTU - Heat Control Board - Fault Codes