Gas Furnace - No Inducer Fan Operation - Code 3

Gas Furnace: TUX/TDX 2-Stage

Re: Flashing Code 3 / Inducer Fan Not Running

Code 3 = Pressure switch fault

There are two pressure switches on this furnace, one for low speed fan and one for high speed.

A Code 3 will result from either of the following conditions:

► If either pressure switch is in the "closed" position when a call for heat is initiated, the control board will flash a Code 3 and NOT power the inducer motor.


Qty Possible Causes (From Most to Least Likely):
1 Bad Pressure Switch
Bad Inducer Motor / Capacitor
ADPS Switch Set Too Low
Bad Control Board


CHECKOUT:

1. Check Controller


2. Check Inducer Motor


3. Check Pressure Switch Contacts


4. ADPS Switch Setting



Article ID: 235
Last updated: 3 Mar, 2017
Revision: 8
Equipment -> Gas Furnaces -> Trane -> TUX2/TDX2 -> Gas Furnace - No Inducer Fan Operation - Code 3