Gas Furnace: TUX/TDX 2-Stage
Re: Flashing Code 3 / Inducer Fan Not Running
Code 3 = Pressure switch fault
There are two pressure switches on this furnace, one for low speed fan and one for high speed.
A Code 3 will result from either of the following conditions:
	- Pressure switch contacts "closed" when they should be open.
- Pressure switch contacts "open" when they should be closed.
► If either pressure switch is in the "closed" position when a call for heat is initiated, the control board will flash a Code 3 and NOT power the inducer motor.
	
		
			| Qty | Possible Causes (From Most to Least Likely): | 
		
			| 1 | Bad Pressure Switch | 
		
			|  | Bad Inducer Motor / Capacitor | 
		
			|  | ADPS Switch Set Too Low | 
		
			|  | Bad Control Board | 
	
CHECKOUT:
1. Check Controller
	- Activate a call for heat from the thermostat (confirm 24VAC between "W" and "C")
	
	
2. Check Inducer Motor
	- With "W' energized, check for 120V power at the inducer motor wiring plug:
	
		- Between "White" and "Red" (Low Speed Fan)
- Between "White" and "Black" (High Speed Fan)
		
		
 
3. Check Pressure Switch Contacts 
	- With "W" energized:
- Check for 24VAC from both sides of each pressure switch to "C".
	
		- Power on both sides = Switch Closed --> Remove one wire from the switch and re-check power to inducer.
- Power on only one side = Switch Open
 
- Both Switches Open and No Power to Inducer = Bad Control Board
4. ADPS Switch Setting
	- The ADPS switch will sometimes fail to re-open when set for the lowest setting.