Heat Pump Locked-Out - Heating

York Package Heat Pumps: BHZ

Re: Compressor not Running / Unit Locked-Out


Safeties:

There is a high pressure switch and a low pressure switch wired in series to the "Pressure Switch" terminals on the defrost board.

Either switch opening with a call for "Y" will cause the heat pump to enter a "lockout".

► There is no LED on the board to indicate a lockout status.


Qty Possible Causes (From Most to Least Likely):
Loss of Refrigerant Charge
Refrigerant Over-Charge
Bad Indoor Blower
Clogged Air Filter
Clogged Indoor Coil
Bad Expansion Valve

CHECKOUT:

1. Check Power


2. Check Operation


3. Check Safety Circuit


4. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 75-100 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge

5. Check Defrost




Article ID: 224
Last updated: 30 Jan, 2023
Revision: 17
Equipment -> Package Units -> York -> BHZ -> Heat Pump Locked-Out - Heating