York 97% Modulating Gas Furnace: YP9C
Re: Flashing Code 5
Flashing Code 5 = Rollout Switch or Condensate Pressure Switch
The rollout switches and the condensate pressure switch are wired in series, so either switch opening during a call for heat will cause a Code 5.
Qty |
Possible Causes (From Most to Least Likely): |
2 |
Improper Drainage |
|
Bad Switch |
|
Bad Transducer |
|
Rollout Switch Tripped |
CHECKOUT:
1. Check Rollout Switches
- Reset the furnace by cycling power.
- Start a call for heat by energizing "W".
- Monitor the LED on the furnace board for lockout indication.
- If board immediately goes into a Code 5, press the reset button on each rollout limit and retry.
2. Monitor Condensate Switch Pressure
- Connect a pressure gauge to the low pressure switch hose.
- Monitor the pressure as the system operates.
3. Check Condensate Drainage
- Check drain hoses from vent coupling.
- If installed horizontally, make sure drains are sloped downward.
- Make sure vent coupling is installed with arrow pointing away from furnace.
- Check drain hoses from inducer and collector box.
- Make sure all drain hoses are clear and have a downward slope.
- ! Make sure there is an "Air-Gap" in the PVC drain immediately upon exiting the furnace !
- The collector box is internally-trapped.
- Any trap in the drain after the collector box before an air gap will cause drainage issues.
- In extreme cold conditions be cautious of Frozen Drains.