Oil Furnaces
Re: Test Procedure / Checkout Steps
1. Check Oil Supply
- If the furnace is running, turn the thermostat off and allow the furnace to cool.
- Turn off power to the furnace.
- Remove the oil supply line from the nozzle assembly.
- Gently bend the supply line to be able to spray oil into a cup.
- Place a jumper across the thermostat input to the controller.
- Re-apply power to the furnace.
- If the burner does not start, press the reset button on the primary control to reset.
- Allow the furnace to pump oil into a cup for up to 5 seconds (stop by turning off power).
- Oil stream should start immediately with the pump motor (except newer models with a delay solenoid valve).
- Oil stream should be continuous and have adequate pressure.
- Oil stream should be solid red (white foam indicates air).
2. Check Transformer & Electrodes
- TEST TRANSFORMER
- Turn off power to the furnace.
- Un-hook power wires to the ignition transformer.
- Hook-up a "Transformer Tester" to the transformer power wires.
- Test the Transformer.
- TEST ELECTRODES
- Remove the Electrode / Nozzle assembly from the burner.
- Use a well-insulated pair of pliers to hold the Electrode / Nozzle assembly on the transformer.
- Use a jumper wire to Ground the Electrode / Nozzle assembly.
- Power the transformer with the "Transformer Tester".
- Observe the electrodes for a proper spark pattern.
3. Clean Cad Cell
4. Check / Replace Nozzle
- If the nozzle has not been replaced in the past year, it is best to go ahead and install a new nozzle.
- Lift the ignition transformer to expose the electrode/nozzle assembly.
- Remove the "keeper" ring from the electrode/nozzle assembly.
- Note the adjustment position of the nozzle assembly.
- Loosen the positioning screw if necessary.
- Remove the electrode/nozzle assembly.
- Replace the nozzle.
- Be Aware! When you loosen the nozzle, oil will run out of the assembly.
5. Check Electrode Adjustment
- Use the diagram to the right as a general rule-of-thumb.
6. Check Ignition/Burner
- Re-install the the nozzle assembly in the furnace.
- Lock the nozzle assemble back in the proper position.
- Re-install the locking nut.
- Re-attach the oil line to the nozzle assembly.
- Allow the burner to fire normally.