York Heat Pump - Not Defrosting / Frozen

York Heat Pump: YMA

Re: Not Defrosting / Frozen

These units use a Demand Defrost control board.

The board uses an Ambient (outdoor) Sensor and Liquid Line Sensor to determine the proper conditions for defrost to occur.

VERY IMPORTANT! The YMA heat pump was originally produced with R-22 refrigerant, then switched to R410a. CHECK THE NAMEPLATE BEFORE ADJUSTING CHARGE!


Qty Possible Causes:
3 Bad Liquid Line Sensor
1 Bad Condenser Fan Motor
Bad Fan Capacitor
1 Bad Defrost Board
Low Refrigerant Charge
Bad Expansion Valve


CHECKOUT:

1. Check Outdoor Fan


2. Test Defrost Cycle


3. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 75-100 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge
R-22
  • 25-35 Suction
  • 160-220 Discharge
  • 36-65 Suction
  • 170-260 Discharge

4. Check Liquid Line Sensor


5. Check Ambient Sensor