York Heat Pump - Not Defrosting / Frozen

York Heat Pump: YMA

Re: Not Defrosting / Frozen

These units use a Demand Defrost control board.

The board uses an Ambient (outdoor) Sensor and Liquid Line Sensor to determine the proper conditions for defrost to occur.

♦ VERY IMPORTANT! The YMA heat pump was originally produced with R-22 refrigerant, then switched to R410a. CHECK THE NAMEPLATE BEFORE ADJUSTING CHARGE!


Qty Possible Causes:
3 Bad Liquid Line Sensor
1 Bad Condenser Fan Motor
Bad Fan Capacitor
1 Bad Defrost Board
Low Refrigerant Charge
Bad Expansion Valve


CHECKOUT:

1. Check Outdoor Fan


2. Test Defrost Cycle


3. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 75-100 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge
R-22
  • 25-35 Suction
  • 160-220 Discharge
  • 36-65 Suction
  • 170-260 Discharge

4. Check Liquid Line Sensor


5. Check Ambient Sensor