Honeywell W7340 Economizer - Fault Codes

Honeywell W7340 Economizer Module

Re: Fault Codes / Status Codes

The status LED is visible through a hole in the device cover. A priority-based LED flash sequence indicates a detected fault.

► All pulse counts are based on the number of times the light pulses off

► In the event of a Communications Failure, the LED pulses on for 0.25 seconds every 2 seconds.

Pulses Description
8 Mixed Air Temperature Sensor Fault
7 Outdoor Air Temperature Sensor Fault
6 Outdoor Air Humidity Sensor Fault
4 Return Air Temperature Sensor Fault
3 Return Air Humidity Sensor Fault
2 Indoor Air Quality Sensor Fault
1 Actuator Fault



Article ID: 212
Last updated: 7 Feb, 2017
Revision: 5
Equipment -> Rooftop Units -> Honeywell W7340 Economizer - Fault Codes