Heat Control Board Flashing Code 3

Trane Reliatel Rooftop Units 

Re: Heat Fault Code 3

Reliatel gas/electric rooftop units have a Heat Control Board as well as the Reliatel Control Board.

There are several version of the Heat Control Board, but two main varieties: 1) Spark ignition and 2) Hot Surface ignition.

The Heat Control Board has an LED for displaying status & fault information. It is very common for the heat faults to not be shown anywhere on the Trane diagrams.


Code 3 = Pressure Switch Fault

The pressure switch should close when the inducer motor starts for a call for heat. A code 3 is generated when the switch fails to close.


Qty Likely Causes of Code 1 (from most to least likely):
1 Bad Inducer Capacitor
Bad Inducer Motor
Bad Pressure Switch
Bad Heat Control Board


Article ID: 209
Last updated: 6 Feb, 2017
Revision: 1
Equipment -> Rooftop Units -> Trane -> Heat Control Board Flashing Code 3
https://ghac.makekb.com/entry/209/