CHECKOUT:
1. Check Basic Operation
- Start the furnace with a call for heat from the thermostat.
- Ensure that the inducer motor starts and runs properly.
- Ensure that ignition takes place properly.
- Observe furnace operation for at least 5 minutes.
- Monitor 24VAC between "W" and "C" on the LTB.
- Make sure burners do not cycle off during the heat cycle.
- "W" drops-out when burners cycle-off = Thermostat Cycling
- 24VAC present on "W" when burners cycle-off = Safety Trip --> Check control board diagnostics
2. Check Temperature Rise
- Check the return air temperature entering the furnace.
- Unusually low return air temperature = Cold Air Infiltration --> Check Ductwork
- Check the supply air temperature near the furnace.
- Compare the actual temperature rise to the furnace rated temperature rise.
3. Check Air Filter & Coil
- Remove the air filter and recheck temperature rise.
4. Check Gas Pressure
- De-energize the call for heat and allow the furnace to cool.
- Turn off power to the furnace and close the gas safety shut-off.
- Hook-up a gas pressure gauge to the manifold (leaving) test port on the gas valve.
- Open the gas safety shut-off valve and re-apply furnace power.
- Activate a call for heat and monitor the manifold gas pressure when the gas valve opens.
- Natural Gas = 2.5" w.c. minimum to 3.5" w.c. maximum
- LP Gas = 9" w.c. minimum to 11" w.c. maximum
- Gas Pressure Low --> Adjust as necessary
- Gas pressure won't come-up --> Check inlet gas pressure
5. Check Indoor Airflow
- Check airflow at the supply registers in the space.
- Unusually low airflow = Ductwork problems
6. Check Space Sq. Ft.
- Calculate the approximate square footage of the space being conditioned by the unit.
- Sq. Ft. = Length X Depth
- For example: A single story home that is approximately 50' long and 25' deep.
- Length (50) X Depth (25) = 1250 sq. ft.
- Use the following table to determine if the equipment is properly sized.
EQUIPMENT |
CONDITIONED SPACE |
BTU Output |
Worst Case* |
Best Case** |
48,000 - 54,000 |
600 sq. ft. |
1,200 sq. ft. |
64,000 - 72,000 |
800 sq. ft. |
1,600 sq. ft. |
72,000 - 81,000 |
900 sq. ft. |
1,800 sq. ft. |
80,000 - 90,000 |
1,000 sq. ft. |
2,000 sq. ft. |
96,000 - 108,000 |
1,200 sq. ft. |
2,400 sq. ft. |
112,000 - 130,000 |
1,400 sq. ft. |
2,800 sq. ft. |
- * Worst Case = Very Loose Construction with Little to No Insulation
- ** Best Case = Very Tight Construction, Heavily Insulated or Foamed