Trane - Furnace Lockout Codes

Trane Gas Furnaces: TUD / TDD /TUX / TDX

Re: Furnace Lockout Codes / Diagnostic Codes

INTEGRATED FURNACE CONTROL - ERROR CODES
Flashing Slow Normal - No call for heat
Flashing Fast Normal - Call for heat
On Replace Control
Off Check Power
2 Flashes Lockout due to re-tries
3 Flashes Pressure switch fault (open or closed)
4 Flashes Open limit circuit
5 Flashes Flame sensed with no call for heat
6 Flashes Reversed polarity, low voltage or poor ground
7 Flashes Gas valve circuit error
8 Flashes Low flame signal
9 Flashes Check Ignitor, Possible grounding problem



Article ID: 192
Last updated: 3 Mar, 2017
Revision: 7
Equipment -> Gas Furnaces -> Trane -> TUD/TDD -> Trane - Furnace Lockout Codes
https://ghac.makekb.com/entry/192/