Yorkguard VI - Low Discharge Temperature (Heating)

York Heat Pump: Yorkguard VI

Re: Low Discharge Temperature (Heating)

The status lights on the module will indicate as follows: Red = On, Green = 6 Flash.


Qty Possible Causes:
Tripped Breaker
1 Bad Capacitor
Bad Compressor
1 Bad Contactor
1 Service Disconnect
Burnt Compressor Terminals
1 Bad Discharge Sensor
Extreme Low Outdoor Temperature

CHECKOUT:

1. Check Outdoor Unit


2. Check Disconnect, Breaker & Compressor


3. Check Contactor


4. Check Pressures & Temperatures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 70-100 Suction
  • 220-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge

5. Check Discharge Sensor


► If necessary, you can disable the discharge temperature sensor and the associated fault codes. (Confirm with Supervisor first.)