58ZAV - Flashing Code 31

Carrier 80% Gas Furnaces: 58ZAV

Re: Flashing Code 31 / Fault Code 31

Light Pattern = 3 Short Flashes + 1 Long Flash (- - - , —)

Code 31 = Pressure Switch Failed to Close

On Carrier 80% Furnaces, the Pressure switch is wired in series with several other possible vent safeties, including a Blocked Vent Switch, Draft Safety Switch, Auxiliary Limit and Low Gas Pressure Switch.

Therefore, a Fault Code 31 is caused by one of the following:


Qty Possible Causes:
Blocked Vent
Bad Pressure Switch
Bad Inducer Motor
Item Stuck in Inducer Motor
Bad Ignition Control
Low Gas Pressure

CHECKOUT:

1. Check Furnace Operation


2. Check Inducer Motor


3. Check Safety Circuit