Carrier 80% Gas Furnaces: 58ZAV
Re: Flashing Code 31 / Fault Code 31
Light Pattern = 3 Short Flashes + 1 Long Flash (- - - , —)
Code 31 = Pressure Switch Failed to Close
On Carrier 80% Furnaces, the Pressure switch is wired in series with several other possible vent safeties, including a Blocked Vent Switch, Draft Safety Switch, Auxiliary Limit and Low Gas Pressure Switch.
Therefore, a Fault Code 31 is caused by one of the following:
- Pressure Switch failed to close or re-opened after closing.
- Draft Safety Switch Open
- Blocked Vent Switch Open
- Auxiliary Limit Switch Open
- Low Gas Pressure Switch Open
Qty |
Possible Causes: |
|
Blocked Vent |
|
Bad Pressure Switch |
|
Bad Inducer Motor |
|
Item Stuck in Inducer Motor |
|
Bad Ignition Control |
|
Low Gas Pressure |
CHECKOUT:
1. Check Furnace Operation
- Start furnace with a call for heat.
- If there is 24V on "W" at power-up, the furnace will run the blower for 90 seconds and flash a Code 12.
- Inducer motor should start and run.
2. Check Inducer Motor
- With a call for heat, check for 115VAC between the Black and White wires of the 3-pin plug for the inducer motor.
- No Power = Bad Control Board
- Power + No Inducer = Bad Inducer / Capacitor or Blocked Inducer Wheel
3. Check Safety Circuit
- Check for 24VAC between "24V Com" and the Orange wire on Pin #3 of the 9-pin plug.
- No Power = Bad Control Board
- Check for 24VAC between "24V Com" and the Yellow wire on Pin #4 of the 9-pin plug.
- Power on Pin #3 + Power on Pin #4 + Code 13 = Bad Control Board
- Power on Pin #3 + No power on Pin #4 = Open Circuit ⇒ Check Each Switch
- Draft Safety Switch
- Check for 24VAC between "24V Com" and both sides of the Draft Safety Switch.
- Power on Both Sides = Switch OK
- Power on One Side Only = Open Switch
- Blocked Vent Switch
- Check for 24VAC between "24V Com" and both sides of the Blocked Vent Safety Switch (if used).
- Power on Both Sides = Switch OK
- Power on One Side Only = Open Switch ⇒ Check Venting System!
- Auxiliary Limit
- Check for 24VAC between "24V Com" and both sides of the Auxiliary Limit Switch (horizontal or counterflow models - mounted in blower compartment).
- Power on Both Sides = Switch OK
- Power on One Side Only = Open Switch ⇒ Check Blower Motor
- Pressure Switch
- Check for 24VAC between "24V Com" and both sides of the Pressure Switch (if used).
- Power on Both Sides = Switch OK
- Power on One Side Only = Open Switch ⇒ Check Pressure Switch
- Low Gas Pressure Switch
- Check for 24VAC between "24V Com" and both sides of the Low Gas Pressure Switch (if used).
- Power on Both Sides = Switch OK
- Power on One Side Only = Open Switch ⇒ Check Gas Pressure