VisionPro Redlink - Aux Heat Settings

Honeywell Redlink VisionPro: TH8320R, TH8321R

Re: Heat Pump Aux Heat Settings

The New VisionPro thermostat allows a technician to adjust how the Auxiliary Heat cycles when configured for a Heat Pump.


CONFIGURE THERMOSTAT

1. ENTER "INSTALLER SETUP"


2. CHANGE BACKUP HEAT SETTINGS

Setup# Description Options
301 CONTROL OPTIONS Basic, Advanced
309 BACKUP HEAT DROOP "Comfort", 2-15º
311 UPSTAGE TIMER BACKUP HT Off, 30 Min-16 Hrs

Once changes have been made, press "Done".


Backup Heat Droop

A Backup Heat Droop is available for any system with 2 heating types. For example:

The options are: 

For example, if the Backup Heat Droop is set to 2 °F (1.0 °C), the indoor temperature must be 2 °F (1.0 °C) away from the setpoint before the backup heat turns on.

The Backup Heat Droop restricts backup heat during the following conditions:


Backup Heat Upstage Timer

The Backup Heat Upstage Timer is available for any system with 2 heating types and the Backup Heat Droop is set to 2 °F (1.0 °C) or higher.

Backup Heat Upstage Timer options are Off, 30 minutes to 16 hours. Default is Off.

Backup heat is not used unless the indoor temperature drops to the Backup Heat Droop setting or the Backup Heat Upstage Timer expires, whichever occurs first.

The upstage timer starts when the highest stage of the previous equipment type turns on.