Package Heat Pump - High Electric Bills

York Package Heat Pump: Heating

Re: High Electric Bill

When the customers reports an electric bill that is much higher than normally, that typically means that the auxiliary heaters are operating more than normal.

► The blower and auxiliary heaters are typically working normally or the customer would also be experiencing no heat.


Qty Possible Causes:
Bad Capacitor
1 Control Lockout (High or Low Pressure)
Bad Compressor
Defrost Problem
Bad Control Board
Unit Mis-Wired
Low Refrigerant Charge
Bad Expansion Valve
Thermostat Issue
Ductwork Problem


CHECKOUT:

1. Check Power


2. Check Compressor Operation


3. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R22
  • 20-40 Suction
  • 150-225 Discharge
  • 40-75 Suction
  • 170-260 Discharge
R410A
  • 75-100 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge

4. Check Compressor Discharge Temperature


5. Check Air Temperature Rise


6. Check Thermostat Aux Ht Settings (New VisionPro 8000)




Article ID: 164
Last updated: 30 Jan, 2023
Revision: 25
Equipment -> Package Units -> York -> Package Heat Pump - High Electric Bills