Rheem Heat Pumps: RPNL/RPQL
Re: Lockout Codes
| "L" Terminal Output | |
| Flashes | Description |
| 1 | Compressor running extremely long cycles |
| 2 | Low or High Pressure control trip |
| 3 | Unit short cycling |
| 5 | Compressor will not run |
| 8 | Control mis-operation |
| 9 | Low control voltage |
| 7-Segment Display Codes | ||
| 0 | Standby | No call for operation |
| c | Call on Y1 | 1st Stage Unit Operation |
| C | Call on Y2 | 2nd Stage Unit Operation |
| d | Defrost | Unit is in Defrost Mode |
| d (flash) | Abnormal Defrost | |
| F | ICC Fuse Open | Low voltage short |
| 21 | Low pressure trip (auto reset) | |
| L21 | Low Pressure Lockout (hard lockout) | |
| 23 | High Pressure Trip (auto reset) | |
| L23 | High Pressure Lockout (hard lockout) | |
| 25 | Bad OD Temperature Sensor | Control will continue to operate |
| 27 | Abnormally Low Line Voltage | |
| 28 | Abnormally High Line Voltage | |
| L5 | Compressor Lockout (hard lockout) | |
Hard Lockout Reset Methods:
FAULT RECALL
To enter FAULT RECALL mode press both TEST and SW2 buttons at the same time with insulated probes for 1 second and release.
CLEAR FAULT HISTORY
To clear FAULT HISTORY press both TEST and SW2 buttons at the same time with insulated probes for 5 seconds and release.