Nordyne / Partners Choice Package Units: R4GA
Re: Flashing Code 1 - Open Limit Circuit
The R4GA package unit has two limits wired in series:
- Primary Heat Exchanger Limit (auto reset) - 165 deg
- Burner Roll-Out Limit (manual reset)
Possible Causes (From Most to Least Likely):
- Primary Limit Open
- Low Airflow
- Dirty Filter
- Clogged Evaporator
- No Blower Operation
- Restricted Ductwork
- Over-Fired
- Bad Limit
- Roll-Out Switch Open
- Bad Heat Exchanger
- Bad Limit
- Bad Control Board
CHECKOUT
Test Limit Circuit
- With a call for heat (24VAC on "W"), check for power through the limit circuit.
- Check for 24VAC power at the control board molex plug on terminal 3 and terminal 8.
- Check between "C" and terminal 3, then between "C" and terminal 8.
- Check Limits
- Without pulling wires off limits (to avoid accidental reset), check for 24VAC power between "C" and each side of each limit.
- Power on one side of the limit and not the other = Open Limit