York Gas Furnace - Code 3

York 90% Gas Furnace

Re: Flashing Code 3

Flashing Code 3 = Furnace Pressure Switch failed to close on a call for heat.


Vent

All 90% gas furnaces have a pressure switch to monitor negative pressure from the inducer motor. If the venting system becomes clogged or restricted, the inducer motor will not be able to push enough exhaust and produce adequate negative pressure.

Intake

On 90% gas furnaces with a sealed combustion box, the pressure switch(es) will typically have a 2-hose connection - one hose to the inducer (-) and one to the burner box (+). This provides a differential pressure that protects against a restricted vent or intake pipe.


Qty Possible Causes (From Most to Least Likely):
1 Water in the vent (improper slope)
Water in inducer (clogged drain)
1 Bad Inducer Motor
Bad Pressure Switch
Clogged / Frozen Drain
1 Water in Pressure Hose
Item Stuck in Inducer Motor
Bad Ignition Control


CHECKOUT:

1. Check Control Board


2. Check Inducer Motor


3. Check Pressure Switch


4. Check Condensate Drainage